Thứ Ba, 21 tháng 6, 2016

Transmitter EL3060 ( CO , CH4 analyzers) + URAS26_ABB


Tên VT
Mô tả chi tiết VT


Transmitter EL3060 ( CO , CH4 analyzers) + URAS26_ABB
Transmitter: Analyser: AT: Infrared Analyzer
Model/Series : EL 3060
EL3060-Uras26 NDIR with separate gas streams for CH4 and CO respectively in IP54 housing suitable for Zone 1 and 2 area class.
1st Gas Path in Uras26
CH4 range: 0.. 1.0 vol%.
2nd Gas Path in Uras26
CO range: 0...0.5 %vol
EL3060 Housing (Ex-d)
Uras26 Infrared Photometer (Ex-d)
Power Supply 100...240 V, 50...60 Hz
Analog/digital outputs
1. 1st Gas Path
CH4: Measuring range: 0-10000 ppm (0 ~ 1.0vol%)
Accuracy: ±1%
Design Temp&Press :410ºC & 3.4 MPa
Operating Temp&Press :360ºC & 3.02 MPa
Density :              kg/m3
Water Content :32.90 mol%
Outward Distance : 70m
Fluid name:  Process gas
Fluid state: gas
Viscosity: mPa.s
Range  for CH4 analyzer sample point :
Component 1: Ar          0 ~ 2%
Component 2: CH4       0 ~ 2 %
Component 3:CO          0 ~ 20%
Component 4:CO2        0 ~ 20 %
Component 5: H2          0 ~ 80%
Component 6: N2          0 ~ 40 %
Normal Value  for CH4 analyzer sample point :
Component 1: Ar           0.28%
Component 2: CH4        0.60  %
Component 3:CO           13.74 %
Component 4:CO2         8.45 %
Component 5: H2           53.13 %
Component 6: N2           23.80%
Service:  Reformer gas Outlet E04209


2. 2nd Gas Path
CO :  Measuring range: 0-5000 ppm ( 0 ~ 0.5vol%)
Accurac: ±1%
Design Temp&Press :300ºC & 3.4 MPa
Operating Temp&Press 228ºC & 2.86 MPa
Density :              kg/m3
Water Content :23.91 mol%
Outward Distance : 80m
Fluid name:  Process gas
Fluid state: gas
Viscosity: mPa.s
Range for CO analyzer sample point  :
Component 1: Ar             0 ~ 2%
Component 2: CH4        0 ~ 2%
Component 3:CO           0 ~ 1%
Component 4:CO2         0 ~ 40%
Component 5: H2           0 ~ 80%
Component 6: N2           0 ~ 40%
Normal Value  for CO analyzer sample point :
Component 1: Ar           0.25%
Component 2: CH4        0.53 %
Component 3:CO           0.30%
Component 4:CO2         19.27%
Component 5: H2           58.67 %
Component 6: N2           20.98%
Service:  Shift gas to E04213
Power supply: 230V AC
Output signal: 4-20mA for CH4 and CO
Calibration report
Accuracy: ±1%
Protection degree: IP41
Electrical class: EEx d IIC T4
Electrical connection:  2X1/2"NPT
Sampling
Sample inlet port: 1/2"NPT
Sample vent: atmos
Wetted parts material: 316L
Package
Sampling heat: yes
Pre-treatment: yes
Cabinet: yes

Không có nhận xét nào:

Đăng nhận xét

Hỗ trợ trực tuyến
Nguyễn Thị Xuân Đào - Sales Engineer Chào mừng quý khách đã đến với tự động hóa . Hãy liên hệ ngay với chúng tôi để được hỗ trợ giá tốt nhất
email: kendy0209@gmail.com
Hotline: 0989.073.182 Skype: mskendy